Power & phase

Power Factor Calculator

Power factor equals real power divided by apparent power. Reactive power and phase angle follow from the same right-triangle relationship.

Calculate power factor, reactive power, and phase angle from real and apparent power.

Enter values

Calculated result

Power factor result

Calculating…

Calculated locally in your browser

Planning math only. Verify equipment specifications and installation requirements separately.

Power factor relationship diagramAn original simplified phase diagram paired with the current calculator result.V · I · PF · PHASERESULTCalculated locallyFORMULA VISIBLEINPUTS EDITABLE
Power Factor Calculator relationship diagram. The illustration supports the text result; it is not a wiring or installation drawing.

What this calculator returns

Real power cannot exceed apparent power in this model. Use measured values from the same operating condition.

Formula and variables

The calculation runs entirely in your browser. Static formulas, definitions, examples, and tables remain readable without JavaScript.

Formula

PF = P/S; Q = √(S² - P²); φ = cos⁻¹(PF).

P
Real power, in watts or kilowatts.
S
Apparent power, in volt-amperes or kilovolt-amperes.
V
RMS voltage; line-to-line voltage in three-phase modes.
I
Line or circuit current, in amperes.
PF
Power factor, expressed as a ratio from greater than zero through one.
Q
Reactive power, in volt-amperes reactive.

P is real power, S is apparent power, Q is reactive power, and φ is phase angle.

Worked example

Worked example inputs
InputValue
Real power8 kW
Apparent power10 kVA

8 kW divided by 10 kVA gives PF 0.8, 6 kVAR, and a phase angle of about 36.87°.

Reference table

Phase relationships derived from the steady-state real and apparent power equations used by these calculators.
SystemApparent powerReal powerVoltage entry
DCS = V × IP = V × ICircuit voltage
Single-phase ACS = V × IP = V × I × PFRMS circuit voltage
Balanced three-phase ACS = √3 × VLL × IP = √3 × VLL × I × PFLine-to-line RMS voltage

Frequently asked questions

Can real power be greater than apparent power?

No in this magnitude model. The entered kW must not exceed kVA because power factor cannot exceed 1.

What does the phase angle result mean?

It is the arccosine of power factor in the displayed power triangle, not a time-domain waveform analysis.

Assumptions and limitations

  • Magnitude-only power triangle.
  • No capacitor-bank recommendation.

Method and sources

Review the electrical formulas, calculation methodology, and reference tables for the references most relevant to this calculation. The broader technical sources index records source scope and verification. Last reviewed .