Educational reference

AWG reference

This reference computes nominal AWG diameter from the logarithmic gauge equation, then computes area as pi times diameter squared divided by four. It follows the standard AWG geometry relationship and the NIST conductor references listed on the Sources page.

Computed nominal AWG solid-wire diameter, cross-sectional area, and circular-mil values from the standard mathematical relationship.

Geometry only. These values do not establish ampacity, insulation outside diameter, or metric conductor equivalence.

Nominal solid-conductor geometry calculated from the AWG mathematical relationship
AWGDiameter (mm)Area (mm²)Circular mils
4/011.6840107.2193211,600
3/010.404985.0288167,806
2/09.265867.4309133,077
1/08.251553.4751105,535
17.348142.407783,693
26.543733.630866,371
45.189421.150641,741
64.115413.301826,251
83.26368.365616,510
102.58825.261210,383
122.05253.30886,530
141.62772.08094,107
161.29081.30872,583
181.02370.82301,624
200.81180.51761,022
220.64380.3255642
240.51060.2047404

Calculation method

Diameter in inches equals 0.005 × 92 raised to (36 − n)/39. Area is then calculated from πd²/4. For 1/0 through 4/0, the gauge index continues through 0, −1, −2, and −3.

Convert AWG and metric conductor area, calculate resistance for an AWG conductor, or estimate voltage drop by conductor size.